Switch 57

57

Bumper Lane Opto

Matrix column 5, row 7 ·  

Wiring

Column 5
Green-Black J206-5 · U20-14
Row 7
White-Violet J208-8 · U19-5

Parts

Location

Owner's hint
Opto sensor (transmitter + receiver). Check +12 V and ground to the opto board, and that nothing blocks the beam. (owner's experience, not the manual)

Service log

 

Everything you record stays on this device.

Service notes: In the switch matrix at column 5 (J206-5, U20-14) and row 7 (J208-8, U19-5). An opto pair: the LED side runs from 12 V through a series resistor on the small board, the phototransistor pulls the row. A phone camera shows the LED as a glow; a blocked, dusty or misaligned opto reads closed. One switch that fails T.1 is its gap, the wire at the lug or its diode; a shorted diode makes the whole column or row misread. A whole column dead is U20 or the J206 pin, a whole row is the row comparator. A3 Switches and optos